In this study, to develop angle ring pressboards for high voltage transformers, the radius and thickness are modified under the conditions of temperature and humidity. In particular, a pressboard with a thickness of 6 mm and a radius at the angled part were investigated based on the simulation of the principal stress from the angled optimization profile shape. As a result, by the appropriate application of a higher temperature, the solid insulation can be improved to reduce the moisture content for an optimized profile angle of a high voltage transformer. This also results in the improvement of the safety factor by 25%. It is determined that the electrical insulation properties of pressboards in high voltage transformers can be enhanced by improving their properties.