TEV 검출에 의한 가스 절연 개폐기의 절연 진단
Insulation Diagnosis of Gas-Insulated Switchgears by TEV Detection
공정배 ( Jeong-bae Kong ) , 길경석 ( Gyung-suk Kil ) , 김성욱 ( Sung-wook Kim )
UCI I410-ECN-0102-2019-500-001347431

Transient earth voltage (TEV) signals propagate on metal surfaces when partial discharge (PD) occurs due to the deterioration of insulation performance in the operation of gas-insulated switchgears (GIS). A TEV sensor has advantages of high sensitivity and convenient installation for detecting PD defects. However, the TEV sensor depends on imports in domestic and detailed studies have not been conducted. In this study, a sensor was designed and fabricated by the TEV principle and its response characteristics were evaluated for detecting PD defects, which were simulated as protrusion on conductor (POC), protrusion on enclosure (POE), and free moving particle (FMP) defects. Finally, the PD-induced TEV signals were measured and phase-resolved partial discharge (PRPD) patterns were analyzed to identify the type of defect.

1. INTRODUCTION
2. METHOD FOR EXPERIMENT
3. RESULTS AND CONSIDERATION
4. CONCLUSIONS
REFERENCES