가연성 외장재를 사용한 건축물의 화재확대방지에 관한 연구
A Study on Fire Spread Prevention of Building using Combusitible Exterior
박성하 ( Park Sungha ) , 권영진 ( Kwon Youngjin )
UCI I410-ECN-0102-2018-500-003787428
This article is 4 pages or less.

Recently, a large fire has occurred through a dry bit, which is a flammable exterior material, in Daebong Green Apartment Fire in Uijeongbu in 2015 and Jecheon Sports Center Fire in 2017. In this study, KS F ISO 5660-1 Cone calorimeter experiment was used to examine the fire risk of dry bit. Also, the performance of the repair and reinforcement materials to prevent fire expansion was examined. As a result, the dry bit is likely to be ignited by internal and external flower gardens, and its combustion rate and calorific value are very high. In addition, the performance of heat resistance such as ALC panel and ceramic board as a repair and reinforcement material has been proved. However, the insulation is expected to require further consideration.