This study was to investigate the effects of soil-structure relative stiffness on the structural characteristics of the cylindrical tank supported by soil. A standard example model of the farm silo rested on the Winkler's subsoil model was used for the analysis of soil-structure coupled system. In this paper, Winkler's constants 4,15 and 100kg/㎠/cm were considered and the bottom plate thicknesses of the farm silo 20, 30, 50,100 and 150cm were adopted. For the given model the effects of bottom plate thickness were the most conspicuous at weakest Winkler's constant 4kg/㎠/cm. While when Winkler's constant is 100kg/㎠/cm, the effect of the bottom plate thickness is almost negligible.
On the other hand, when the bottom plate thickness is more than 100cm, the effects of elastic foundation were almost disappeared. In design practice, it is hoped that the thicknesses of bottom plate should be determined reasonably because of it's considerable effect on the structural characteristics as the 100cm thickness of bottom plate will not be practical value in usual sites.