절연진단법을 이용한 고전압전동기 고정자권선의 절연특성분석
Analysis of Insulation Characteristics for High-voltage Motor Stator Winding using Insulation Diagnostic Test
오봉근 ( Bong Keun Oh ) , 강현구 ( Hyun Goo Kang ) , 김현일 ( Hyun Il Kim ) , 임기조 ( Kee Joe Lim )
UCI I410-ECN-0102-2015-500-001796881
이 자료는 4페이지 이하의 자료입니다.

Insulation diagnostic tests for high voltage motor stator winding were conducted to analyze the insulation characteristics. Test motors were manufactured same factory and year(1996). Insulation characteristics of moisture winding are different from those of deteriorative winding. Insulation resistance and disscipation factor test results are sensitive to moisture winding. AC current, disscipation factor tip-up and PD test results are sensitive to deteriorative winding. Also, Capacitance value for stator winding insulation material has characteristic of increasing in moisture winding.