인공오손에 따른 배전기자재의 건조 및 습윤 섬락에 관한 연구
The Study on the Dry and Wet Flashover Voltages of the Artificially Salt Contaminated Distribution Facilities
김찬영 ( Chan Young Kim ) , 김동명 ( Dong Myung Kim ) , 권태호 ( Tae Ho Kwon )
UCI I410-ECN-0102-2015-500-001796356
이 자료는 4페이지 이하의 자료입니다.

The dry and wet flashover characteristics on the contaminated distribution facilities was investigated. The test were carried out on the suspension insulator, line post insulator, lightning arrester, cut off switch, etc. In the dry state, the flashover voltages of facilities contaminated with B, C, D classes are similar to the non-contaminated ones. However, in the wet state, the flashover voltages of facilities contaminated with B, C, D classes are decreased. The flashover voltages of some few facilities show under the standard value. This results indicate that the high humidity may cause the flashover on distribution facilities.