산업오손에 따른 배전설비 절연물의 전기적 및 재료적 특성
The Electrical and Material Characteristics of the Distribution Facilities Suffered from Industrial Pollution
김찬영 ( Chan Young Kim ) , 정종만 ( Jong Man Jung ) , 이재봉 ( Jae Bong Lee ) , 천성남 ( Sung Nam Chun ) , 김동명 ( Dong Myung Kim ) , 송일근 ( Il Keun Song ) , 김병숙 ( Byung Suk Kim )
UCI I410-ECN-0102-2015-500-001803812
이 자료는 4페이지 이하의 자료입니다.

The distribution facilities, such as suspension insulator, line post insulator, lightning arrester, COS, used for long periods in the industrial pollution area were investigated. The electrical test and the material analyses were performed on the polluted and non-polluted facilities. The low frequency dry flashover voltage of polluted suspension was decreased about 8% in comparison with non-polluted one. The polluted materials turned out with the iron which came from the foundries. The polluted materials turned out with the iron which came from the foundries. This conductive materials decreased the leakage distance, resulting in reducing of electrical properties.