18.97.14.88
18.97.14.88
close menu
Accredited
절연재료 : 고압전동기 고정자 권선의 온도변화에 따른 절연특성 분석
Insulation Materials : Analysis of the Temperature Influence on Insulation Characteristics in High Voltage Motor Stator Windings
공태식 ( Tae Sik Kong ) , 주영호 ( Young Ho Ju ) , 김희동 ( Hee Dong Kim ) , 박태성 ( Tae Sung Park )
UCI I410-ECN-0102-2013-560-002248979

A variety of diagnostic tests are widely applied in the field in industry to evaluate the condition of high voltage (HV) motor stator insulation. In this paper, the influence of temperature on the stator insulation diagnostic tests such as the insulation resistance, AC current, dissipation factor, and partial discharge measurements are studied and reported. The tests are performed with the HV motor stator winding temperature set between 40℃ to 80℃ in 10℃ intervals. It is shown that the AC current, dissipation factor, and partial discharge magnitude steadily increase with temperature, which suggests that temperature must be taken into account in the interpretation of the test results.