보조전극의 배치 및 주파수에 따른 매설지선의 접지임피던스 특성
Characteristics for Ground Impedance of Counterpoise according to Position of Auxi1iay Probe and Frequency
김형준 ( Hyoung Jun Gil ) , 김동우 ( Dong Woo Kim )
UCI I410-ECN-0102-2012-530-003047190
* 발행 기관의 요청으로 구매가 불가능한 자료입니다.

This paper describes the characteristics for ground impedance of counterpoise according to position of auxiliary probe and frequency using the fall-of-potential method and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position of auxiliary probes. In order to analyze the effects of ground impedance due to the distance of the current probe and frequency, ground impedances were measured in case that the distance of current probe was located from I0[m] to l00[m]and the measuring frequency was ranged in 55 [Hz], 128[Hz], 342[Hz], and 51 3[Hz]. The results could be help to determine the position of auxiliary probe when the ground impedance was measured at grounding system.