FDS를 이용한 실내화재 모사의 문제점 -2. 벽면형 및 모서리형 화재
A Numerical Study of a Room Fire for Fire Sizes -2. wall fire and corner fire
고경찬 ( Kyung Chan Ko ) , 박외철 ( Woe Chul Park )
UCI I410-ECN-0102-2009-530-002486290
* This article cannot be purchased.

To confirm the previous finding that FDS predicts a fire growth rate too rapid compared with an experiment in a center fire in a room with an opening, the same computational fluid dynamics was applied to two types of fires, wall fire and comer fire. First the grid size was chosen to eliminate possible numerical errors due to a coarse grid system. Then the two types of fires were simulated for three different fire sizes, 7.65, 21.25, and 51.57kW for each type, which are the same as in the experiment to be compared with. The fires were predicted to grow too fast although the average temperatures and heights of the neutral planes were in good agreement with measurement.