With the three dimensional magnetic field measuring system dealt with in this paper, accurate measurements and analyses of extremely low frequency(ELF) magnetic fields caused by starting and/or operating electric devices and power installations can be conducted. To obtain high performance for lower frequency and spatial components without any distortion, the measuring system is designed as three dimensionally including the multiturn loop-type magnetic field sensors, differential amplifiers and active integrators. As the results of calibration experiments, the frequency response characteristics of the measuring system range from 8[Hz] to about 53[kHz] for each direction of x, y, z axes, and the response sensitivities are 9.54, 9.21, 10.89[mV/μT], respectively. The actual survey experiments by using an oscillating impulse current generator confirm a reliability of the proposed measuring system. Also, through the other experiments by using small-sized induction motors, the magnetic field intensities when starting and steady-state operating mark 15.8, 8.61 [μT] as maximum value, respectively. And those intensities decrease steeply according as the measuring distance increases.