BAC Pilot Plant 를 이용한 겨울철 암모니아성 질소 제거 및 THMs 변화
Removal of Ammonia Nitrogen and Reduction of THMs in Low Temperature by BAC Pilot Plant
강은조(Eun Jo Kang),서영진(Young Jin Seo),이원권(Won Kwon Lee),전병희(Pyoung Hee Chun),이지형(Ji Hyung Lee),윤정효(Jung Hyo Yoon),김동윤(Dong Youn Kim)
UCI I410-ECN-0102-2009-530-005903476
* This article cannot be purchased.

The raw drinking water quality is getting worse because of the winter drought and the conventional treatment system is’nt suitable to obtain the satisfied quality of water. So, the advanced water system, BAC(Biological Activated Carbon) process is said to be effective to remove dissolved organics and ammonia nitrogen. In our study, the BAC pilot plant using Nak-dong river water is tested in low temperature. Following results are found from the study. The ammonia nitrogen removal rate of BAC system using wood-based carbon(PICABIOL) was 99% in 6℃ temperature. Chlorine dosage in wood-based BAC effluent was reduced to 67% of that in sand filtered wate. It resulted from the removal of ammonia nitrogen. Also, THM formed by chlorine addition in wood-based BAC effluent was decreased to 65% of that in sand filtered water. In the case of dual-filter, the removal efficiency of ammonia nitrogen was increased 30% more than in conventional sand filter. According to this result, the ammonia nitrogen load to BAC system could be lessened by the use of dual-filter.